NTI E-MINI-LXOB Mini Environment Monitoring System monitors critical environmental conditions (such as temperature, humidity, and water leakage) that could destroy network components in your server room. When a sensor goes out of range of a configurable threshold, the system will notify you via email, SNMP traps, web-page alerts, a visual indicator (red LED), voice phone calls (via Automatic Voice Dialer System), and SMS messages (via USB 3G modem).
NTI E-MINI-LXOB Mini Environment Monitoring System, Back-up Battery Features:
- Monitor and manage server room environmental conditions over IP.
- Sensors supported:
- 2 temperature/humidity sensors.
- 5 digital inputs sensitive to contact closure.
- Sensors are hot plugable.
- One output relay for control of external devices.
- Relay activates upon alarm or via the user interface.
- Supports IP network video cameras for live view of any facility.
- One integrated view - see different Web cameras side-by-side with physical and environmental parameters.
- Any programmed event can trigger a snapshot from an IP camera.
- Monitor (ping) up to 16 IP network devices.
- Alerts are sent if devices are not responding.
- Two USB ports for connecting USB modem or for downloading log data to USB flash drive, and one USB console port for serial terminal interface.
- Available with optional internal battery backup.
- Alerts are sent when there is a power outage and when power returns.
- Create multiple alerts for any installed sensor.
- Sensor conditions (events) can be configured to trigger alerts by themselves, and/or be used in combination with other events to trigger Smart Alerts.
- Configure up to 50 events.
- Up to 20 Smart Alerts can be configured to use different event combinations to send alert messages.
- Alerts are posted in message log, which is accessible through Web user interface.
- Automatically configures network settings received from a connected DHCP server.
- If a DHCP server is not found, the default static IP address will be used.
- Integrates with various Open Source monitoring packages - Nagios, MRTG and others.
- The unit can be polled via SNMP.
- Linux inside.
- Supports network security scanners.
- Backup and restore system configurations.
- Flexible Zero-RU mounting.
- Mounting tabs included.
- Optional 1RU rackmount kit available; the ENVIROMUX unit can be mounted with the front or rear facing out.
- Optional DIN mounting available.
- Security: HTTPS, SSHv2, SSLv3, IP Filtering, LDAPv3, AES 256-bit encryption, 16-character username/password authentication, user account restricted access rights.
- Use in data centers, co-lo sites, web hosting facilities, telecom switching sites, POP sites, server closets, or any unmanned area that needs to be monitored.
- Optional industrial Mini Environment Monitoring System, Back-up Battery for high temperature environments. This industrial system has the ability to operate and monitor in harsh environments at high temperatures up to 167˚F (75˚C).
Why not buy this NTI E-MINI-LXOB Mini Environment Monitoring System, Back-up Battery today?
NTI E-MINI-LXOB Mini Environment Monitoring System, Back-up Battery Specification:
Temperature/Humidity Inputs- Two female RJ45 connectors for connecting temperature sensors, humidity sensors and/or combined temperature/humidity sensors.
- Two levels of user-defined alerts - non-critical and critical.
- Five screw terminal pairs for connecting dry contact devices and the liquid detection sensor.
- Potential-free.
- Output voltage: +5 V DC
- Current limited to 10 mA
- Maximum resistance to close contact: 300K Ohm
- One screw terminal pair.
- Potential-free relay switch contacts.
- Maximum switching load: 0.5A at 125 VAC, 1A at 30VDC
- Two female USB Type A connectors for connecting USB modem or for downloading log data to USB flash drive.
- One female USB Type B connector for connecting a PC for serial terminal access.
- One female RJ45 connecto.
- 10/100 Base-T Ethernet interface.
- Rechargeable sealed lithium battery.
- Provides back-up for two hours.
- E-MINI-LXOB: 274,783 hours.
- HTTP/HTTPS, SNMP V1/V2c/V3, SMTP, TCP/IP, Syslog, SNTP, DHCP, SSHv2, SSLv3, TLS v1.2, LDAPv3, AES 256-bit, 3DES, Blowfish, RSA, EDH-RSA, Arcfour, IPV6, WAP 2.0
- Compatible with any SNMP management software.
- The unit can be polled via SNMP.
- Operates and configures via HTTP/HTTPS web page, Telnet, SSH, or USB serial interface.
- An IP address can be assigned to the E-MINI-LXOB automatically by a DHCP server.
- Generates SNMP traps, email alerts, and syslog messages.
- Alerts are posted in event log, which is accessible through Web user interface.
- Email alerts can be sent to 17 addresses.
- WxDxH: 5.82x3x1.75 in (148x76x44 mm)
- Optional 1RU rackmount kit available
(E-RK1-2D).- The ENVIROMUX system can be mounted so that the sensor connectors are facing the front or back of the rack.
- 110 or 220 VAC at 50 or 60 Hz via AC adapter.
- Includes 9V, 1.5A adapter.
- Will work with a 12V, 2A adapter.
- Overvoltage and overcurrent protection in the unit and power supply.
- Power consumption: 10 W
- Use the PWR-48V-12V1-6A DC-DC power converter to install the E-MINI-LXOB in a 48V or 24V Telecom environment.
- Operating temperature:
- E-MINI-LXOB: 32 to 104˚F (0 to 40˚C).
- E-MINI-LXOB-IND: 32 to 167˚F (0 to 75˚C).
- Storage temperature: -20 to 176˚F (-20 to 80˚C).
- Operating and Storage Relative Humidity: 17 to 90% non-condensing RH.
- CE, RoHS
- EN51055, EN50121-3-2
- Two years
Data Sheet: NTI E-MINI-LXO-INDD Data Sheet
Users Manual: NTI E-MINI-LXO-INDD Installation and Operation Manual
NTI E-MINI-LXO-INDD Quick Installation Guide