NTI E-DI16DOR16-V22R Digital Input/Output Expander

NTI

$620.00
Part Number:
E-DI16DOR16-V22R
Availability:
In Stock
1:
NTI E-DI16DOR16-V22R Digital Input/Output Expander
2:
Interfaces with the SYSTEM via the RJ45 Sensor Port
3:
Free 15-Day Trial (See below FAQ)
4:
Free Shipping
5:
2-Year NTI Warranty
ADD OPTIONS:

NTI E-DI16DOR16-V22R Digital Input/Output Expander (Normally-Open Relay Contact Outputs)

The E-DI16DOR16-V22R Digital Input/Output Expander enables the connection of up to 16 additional digital sensors and output devices using just one RJ45 Sensor port on an E-2D, E-5D, or E-16D Server Environment Monitoring System (SYSTEM).The E-DI16DOR16-V22R includes digital outputs with an open-collector design for the control of up to 16 relays, solenoids, LEDs, and other devices that operate at voltages between 0-24VDC (maximum 500mA).

The E-DI16DOR16-V22R includes digital outputs with a normally-open SPST relay design for the control of up to 16 different devices that operate at a maximum125VAC (0.5A maximum) or maximum 30VDC (1.0A maximum).

NTI E-DI16DOR16-V22R Digital Input/Output Expander (Normally-Open Relay Contact Outputs) Features:

  • Interfaces with the SYSTEM via the RJ45 Sensor Port
  • Digital inputs:
    • 16 screw terminal pairs for connecting dry contact devices
  • One screw terminal pair for tachometer; 0 to 255 Hz
    • Accepts 26 to 16AWG wire
    • Potential free
    • Voltage range: 0 to +36VDC
    • o Over-voltage surge protected
    • Supports 18-24AWG CAT5/5e/6 cable up to 500 ft. (152.4 m)

Why not buy this NTI E-DI16DOR16-V22R Digital Input/Output Expander (Normally-Open Relay Contact Outputs) today?

NTI E-DI16DOR16-V22R Digital Input/Output Expander (Normally-Open Relay Contact Outputs) Specifications:

  • Adds 16 digital inputs and 16 digital normally-open relay contact outputs to the E-2D/5D/16D
    • Interfaces with the E-2D/5D/16D via the RJ45 Sensor Port
  • Digital inputs:
    • 16 screw terminal pairs for connecting dry contact devices
      • One screw terminal pair for tachometer; 0 to 255 Hz
    • Accepts 26 to 16AWG wire
    • Potential free
    • Voltage range: 0 to +36VDC
    • Over-voltage surge protected
  • Digital outputs:
    • 16 screw terminal pairs for normally-open relay contact outputs
    • Accepts 26 to 16AWG wire
    • Potential free
    • Rated switching load: 0.5A @ 125VAC, 1A @ ±30VDC, 0.5A @ ±48VDC.
    • Galvanic isolation: 1kV
    • Fused
  • Supports CAT5/5e/6 cable up to 500 ft. (152.4 m)
  • Control via SNMP:
    • Requires read-write community configuration.
    • Digital inputs are fixed values (not writable) while output relays are writable.
    • Locate OIDS using a MIB browser.
  • Includes 5V/3A power supply.
  • Current consumption: 75mA @ 5VDC
  • Compatible with E-2D/5D/16D.
  • Available options: desktop unit with wall mounting brackets, 1RU rackmount unit, dual side-by-side rackmount units in 1RU.
  • Dimensions WxDxH:
    • E-DI16DOR16-V2 (desktop): 6.49x3.15x1.75 in (165x80x44 mm)
    • E-DI16DOR16-V22R (1RU rackmount) and E-DI16DOR16-V22R (1RU dual side-by-side rackmount): 19x3.15x1.75 in (486x80x44 mm)
  • Regulatory approvals: RoHS
  • MTBF: 650,166 hrs
  • Operating temperature: 32 to 158˚F (0 to 70˚C)
  • Storage temperature: -4 to 176˚F (0 to 70˚C)
  • Compatible with Fiber Converter/Extender.
    • Use to extend sensor up to 1.2 miles (2 km) from the ENVIROMUX unit.