This NTI E-2D-48V Small Enterprise Environment Monitoring System, 48VDC Power monitors critical environmental conditions (such as temperature, humidity, and water leakage) that could destroy network components in your server room. When a sensor goes out of range of a configurable threshold, the system will notify you via email, SNMP traps, web-page alerts, a visual indicator (red LED), voice phone calls (via Automatic Voice Dialer System), and SMS messages (via email-to-SMS or external USB modem).
NTI E-2D-48V Small Enterprise Environment Monitoring System, 48VDC Power Features:
- Monitor and manage server room environmental conditions over IP.
- Sensors supported by a single E-2D:
- 2 external configurable sensors
- 5 digital inputs sensitive to contact closure
- 8 Remote Temperature/Humidity Sensors over IP
- E-MICRO-TRH(P): 1 integrated temperature/humidity combination sensor, 2 RJ45 ports for external temperature/humidity sensors, 2 digital inputs sensitive to contact closure, optional built-in Power over Ethernet (POE), dual DC power.
- 4 Remote 1-Wire Sensors over IP
- E-1W(P): two RJ11 connectors for daisy chaining many 1-wire temperature/humidity/dew point, thermocouple, or digital input expanders in any combination (up to 24 single-reading 1-wire sensors); two digital inputs sensitive to contact closure; dual DC power; optional Power over Ethernet (POE).
- Use an RJ45 RS485 Sensor Expander to add 8 RJ45 RS485 sensors.
- Use a Digital Input/Output Expander to add 16 digital inputs and 16 digital outputs.
- One output relay for control of external devices.
- Relay activates upon alarm or via the user interface.
- Control output relays via SNMP SET commands to power on/off external devices.
- Supports NTI's IP network video cameras for live view of any facility.
- One integrated view – see different Web cameras side-by-side with physical and environmental parameters.
- Any programmed event can trigger a snapshot from an IP camera.
- Monitor (ping) up to 64 IP network devices.
- Alerts are sent if devices are not responding.
- Linux inside.
- Create multiple alerts for any installed sensor.
- Sensor conditions (events) can be configured to trigger alerts by themselves, and/or be used in combination with other events to trigger Smart Alerts.
- Configure up to 50 events.
- Setup SSH commands to be sent when events are triggered to soft shutdown or reboot machines.
- Up to 20 Smart Alerts can be configured to use different event combinations to send alert messages.
- Configure up to 50 events.
- Alerts are posted in message log, which is accessible through Web user interface.
- Automatically configures network settings received from a connected DHCP server.
- If a DHCP server is not found, the default static IP address will be used.
- Integrates with various Open Source monitoring packages – Nagios and MRTG.
- The unit can be polled via SNMP.
- Two USB ports for connecting USB modem or for downloading log data to USB flash drive, and one USB console port for serial terminal interface.
- Available with optional internal battery backup.
- Alerts are sent when there is a power outage and when power returns.
- Available with optional 24VDC or 48VDC power, or optional built-in Power over Ethernet (PoE).
- Up to five units can be used together to increase the number of sensors connected.
- Cascade up to four E-2D/5D/16D units as slaves to one E-2D/5D/16D master unit via Ethernet connection.
- Each master and slave unit needs its own unique IP address.
- Uses a single Web interface for all systems/sensors connected.
- Cascade up to four E-2D/5D/16D units as slaves to one E-2D/5D/16D master unit via Ethernet connection.
- Dual redundant power supplies for connection to two separate power sources.
- The second power supply is sold separately.
- Optional industrial small environment monitoring system for high temperature environments. This industrial system has the ability to operate and monitor in harsh environments at high temperatures up to 167°F (75°C).
- Optional Self-Hosted Enterprise Environment Monitoring System Management Software for monitoring and configuring up to 3,000 E-2D/5D/16D devices and all connected sensors. Access from anywhere using a web browser on a computer, smartphone, and/or tablet. No clients or special apps to install.
- Flexible Zero-RU mounting.
- Mounting tabs included.
- Optional 1RU rackmount kit available; the ENVIROMUX unit can be mounted with the front or rear facing out.
- Optional DIN mounting available.
- Security: HTTPS, SSHv2, SSLv3, IP Filtering, LDAPv3, AES 256-bit encryption, 16-character username/password authentication, user account restricted access rights.
- Multi-language support – English, German, Chinese, and Japanese.
- Use in data centers, co-lo sites, web hosting facilities, telecom switching sites, POP sites, server closets, or any unmanned area that needs to be monitored.
- Use the E-2D with a wireless router and Wi-Fi Range Extender to create a Wireless Environment Monitoring System.
- Configure, monitor, and receive alerts without the use of a wired network connection
Why not buy this NTI E-2D-48V Small Enterprise Environment Monitoring System, 48VDC Power today?
NTI E-2D-48V Small Enterprise Environment Monitoring System, 48VDC Power Specifications:
RJ45 Sensor Ports
- Two female RJ45 jacks for connecting NTI temperature, humidity, liquid detection, smoke detection, glass break, vibration, motion sensors, and more.
- Two levels of user-defined alerts – non-critical and critical.
- Provides +12 VDC, 100 mA for each port.
Dry Contact Closures
- Five screw terminal pairs for connecting dry contact devices and the liquid detection sensor.
- Potential-free.
- Output voltage: +5 V DC
- Current limited to 10 mA
- Maximum resistance to close contact: 300K Ohm
Output Relay
- One screw terminal pair.
- Potential-free relay switch contacts.
- Normally open / normally closed connection points.
- Maximum switching load: 1A at 125VAC or 30VDC.
USB Ports
- Two female USB Type A connectors for connecting USB modem or for downloading log data to USB flash drive.
- One female USB Type B connector for connecting a PC for serial terminal access.
Ethernet Port
- One female RJ45 connector.
- 10/100 Base-T Ethernet interface.
- Supports full- and half-duplex.
Power Output
- AUX Power
- One screw terminal pair.
- Provides +12 VDC, 500 mA.
Optional Back-Up Battery
- Rechargeable sealed lithium battery.
- Provides back-up for two hours.
MTBF
- E-2D: 229,580 hours.
- E-2DB: 230,693 hours.
Protocols
- HTTP/HTTPS, SNMP V1/V2c/V3, SMTP, TCP/IP, Syslog, SNTP, DHCP, SSHv2, SSLv3, TLS v1.2, LDAPv3, XOAUTH2, AES 256-bit, 3DES, Blowfish, RSA, EDH-RSA, Arcfour, IPV6, WAP 2.0, RADIUS
- Support for XOAUTH2 provides higher security authentication for email accounts (e.g. Gmail).
- Compatible with any SNMP management software.
- The unit can be polled via SNMP.
- Operates and configures via HTTP/HTTPS web page, Telnet, SSH, or USB serial interface.
- Supports Internet Explorer 6.0 and higher, Firefox 1.5 and higher, Netscape 9, Google Chrome, Safari 1.3 and higher for MAC, and Safari 3.0 and higher for PC.
- Multiplatform support: Windows 7/8/10, Windows Server 2008/2012/2016/2019, Solaris, Linux, FreeBSD, and MAC OS 10/11.
- An IP address can be assigned to the E-2D automatically by a DHCP server.
- Generates SNMP traps, email alerts, syslog messages, and SMS messages (via USB 3G modem).
- Alerts are posted in event log, which is accessible through Web user interface.
- Email alerts can be sent to 17 addresses.
- Supports HTTP REST API to poll sensor data with response in JSON format.
Dimensions
- WxDxH: 5.82x3x1.75 in (148x76x44 mm)
- Optional 1RU rackmount kit available
(E-RK1-2D).- The ENVIROMUX system can be mounted so that the sensor connectors are facing the front or back of the rack.
Weight
- E-2D: 1.0 lb (0.45 kg)
Power
- Dual DC power.
- If the first power source fails, the unit will automatically, without interruption, switch over to the second power source before switching to the optional battery backup.
- 100 to 240 VAC at 50 or 60 Hz via AC adapter.
- Includes one country-specific AC adapter. The second AC adapter is sold separately.
- Power consumption: 10W.
- Optional built-in Power over Ethernet (PoE)
- Power over Ethernet standards supported: IEEE 802.3af, 802.3at.
- Proprietary schemes such as Cisco Discovery Protocol are not supported.
- Similar legacy switches and routers will have to use PWR-SPLY-9V3A
- Proprietary schemes such as Cisco Discovery Protocol are not supported.
- If the Power over Ethernet source fails, the unit will automatically, without interruption, switch over to the DC power source.
- Power over Ethernet standards supported: IEEE 802.3af, 802.3at.
- Optional 24VDC power.
- Accepts 9~36VDC (24VDC nominal).
- For installation in a 24V Telecom environment.
- Optional 48VDC power.
- Accepts 18~72VDC (48VDC nominal).
- Use the PWR-48V-12V1-6A DC-DC power converter to install the E-2D in a 48V or 24V Telecom environment.
Environmental
- Operating temperature:
- E-2D: 32 to 140°F (0 to 60°C)
- E-2D-IND: -4 to 167°F (-20 to 75°C)
- Storage temperature: -22 to 140°F (-30 to 60°C).
- Operating/Storage Relative Humidity: 5 to 90% non-condensing RH.
Regulatory Approvals
- CE, RoHS
- EN51055, EN50121-3-2
Warranty
- Two years