NTI E-1W Environment Monitoring System with 1-Wire Sensor Interface monitors critical environmental conditions, such as temperature, humidity, liquid water presence, power, intrusion, and smoke. When a sensor goes out of range of a configurable threshold, the system will notify you via email, web page, network management (SNMP), and/or SMS messages (via email-to-SMS).
The system supports 24 single reading 1-wire sensors in any combination - temperature, humidity, dew point, thermocouple or digital inputs - and 2 separate digital inputs. It functions independently or as an IP-connected remote sensor for the E-2D/5D/16D.
NTI E-1W Environment Monitoring System with 1-Wire Sensor Interface Features:
- Monitor and manage environmental and security conditions over IP.
- Sensors supported:
- 2 digital inputs sensitive to contact closure.
- 2 RJ11 6P4C connectors for daisy-chaining 1-wire temperature/humidity/dew point, thermocouple, or digital input expanders in any combination.
- Up to 24 temperature, thermocouple, or any single reading 1-wire sensor can be connected between both RJ11 connectors.
- Up to 8 temperature/humidity/dew point combination 1-wire sensors can be connected between both RJ11 connectors. Each temperature/humidity/dew point sensor is equivalent to 3 single reading sensors.
- Up to 12 E-DI2-1W digital input expanders can be connected between both RJ11 connectors to allow a maximum of 24 additional digital inputs. Each E-DI2-1W is equivalent to 2 single reading sensors.
- Maximum cable length supported on each connector is up to 600ft (183 m) depending on the configuration and number of connected sensors.
- Use RJ11 splitters (RJ11-3JCK) to daisy-chain 1-wire sensors (sold separately).
- Sensors are hot pluggable.
- The sensors will automatically be detected on power up or a Detect Devices button on the summary page can be selected when logged into the unit.
- Monitors (ping) up to 4 IP network devices - alerts are sent if devices are not responding.
- Sensor conditions can be configured to trigger alerts by themselves, and/or be used in combination with other alerts to trigger one Smart Alert.
- Supports 4 IP network video cameras for live view of any facility.
- Create multiple alerts for any installed sensor.
- Sensor conditions can be configured to trigger alerts by themselves, and/or be used in combination with other alerts to trigger one Smart Alert.
- Configure up to 32 alerts, and one Smart Alert.
- Dual redundant power supplies for connection to two separate power sources.
- The second power supply is sold separately.
- Available with optional Power over Ethernet (POE).
- Integrates with various Open Source SNMP monitoring packages Nagios
- The unit can be polled via SNMP.
- Optional intuitive graphical management software provides an easy-to-use, unified interface for both monitoring and configuring up to 3,000 ENVIROMUX units and all connected sensors.
- Security: HTTPS, SSLv3, AES 256-bit encryption, 16-character username/password authentication, user account restricted access rights.
- Ideal for a wide range of applications including IT infrastructure monitoring, cold storage/freezer monitoring, or any unmanned area that needs to be monitored.
Why not buy this NTI E-1W Environment Monitoring System with 1-Wire Sensor Interface today?
NTI E-1W Environment Monitoring System with 1-Wire Sensor Interface Specification:
RJ11 Sensor Ports- Two RJ11 6P4C jacks for daisy-chaining 1-wire temperature/humidity/dew point, thermocouple, or digital input expanders in any combination.
- Up to 24 temperature, thermocouple, or any single reading 1-wire sensor can be split between both RJ11 connectors.
- Up to 8 temperature/humidity/dew point combination 1-wire sensors can be split between both RJ11 connectors. Each temperature/humidity/dew point sensor is equivalent to 3 single reading sensors
- Up to 12 digital input expanders can be split between both RJ11 connectors to allow a maximum of 24 additional digital inputs. Each digital input expander is equivalent to 2 single reading sensors
- Maximum cable length supported on each connector is up to 600ft (183 m) depending on the configuration and number of connected sensors.
- This maximum includes the cable length of each sensor.
- RJ11 splitters or t-tap boards (RJ11-3JCK) for convenient daisy-chaining are sold separately.
- Two screw terminal pairs for connecting dry contact devices and liquid detection sensors.
- One female Micro USB connector - reserved for future use.
- One female RJ45 connector.
- 10/100 Base-T Ethernet interface.
- HTTP/HTTPS, SNMP V1/V2c, SMTP, TCP/IP, Syslog, SNTP, DHCP, SSLv3, AES 256-bit, 3DES, Blowfish, RSA, EDH-RSA, Arcfour
- SSLv3 has been disabled in the following browser versions and affects HTTPS connection to the E-1W:
- Microsoft Edge
- Firefox Version 34 and newer
- Opera Version 25 and newer
- Google Chrome Version 40 and newer
- Internet Explorer and Safari: all versions allow SSLv3, if there are connection issues check if SSLv3 is manually disabled.
- SSLv3 has been disabled in the following browser versions and affects HTTPS connection to the E-1W:
- Compatible with any SNMP management software.
- The unit can be polled via SNMP.
- Operates and configures via HTTP/HTTPS web page.
- An IP address can be assigned to the E-1W automatically by a DHCP server.
- Generates SNMP traps, email alerts, syslog messages, and SMS messages (via email-to-SMS).
- Alerts are posted in event log, which is accessible through Web user interface.
- Email alerts can be sent to 9 addresses.
- Users can configure the schedule for when they will be alerted.
- Email alerts are not compatible with TLS.
- WxDxH in: 4x3.65x1.37 (102x93x35 mm).
- E-1W:
- Dual DC power provides dual redundancy.
- If the first power source fails, the unit will automatically, without interruption, switch over to the second power source.
- The unit draws power from the source with the highest DC voltage (nominal 5.5V).
- If both sources have exactly the same voltage, it will draw in part from each of them.
- 110 to 240 VAC at 50 or 60 Hz via AC adapter.
- Includes one country-specific AC adapter. The second AC adapter is sold separately (PWR-SPLY-ELC).
- Input voltage: 5.5VDC ±5%
- Dual DC power provides dual redundancy.
- E-1WP:
- Built-in Power over Ethernet and dual DC power provides triple redundancy.
- Power over Ethernet standards supported: IEEE 802.3af, 802.3at.
- Proprietary schemes such as Cisco Discovery Protocol are not supported.
- Similar legacy switches and routers will have to use PWR-SPLY-ELC.
- Proprietary schemes such as Cisco Discovery Protocol are not supported.
- Power over Ethernet standards supported: IEEE 802.3af, 802.3at.
- If the first power source fails, the unit will automatically, without interruption, switch over to the second power source.
- The unit draws power from the source with the highest DC voltage (nominal 5.5V).
- If two or more sources have exactly the same voltage, it will draw in part from each of them.
- Built-in Power over Ethernet and dual DC power provides triple redundancy.
- 110 to 240 VAC at 50 or 60 Hz via AC adapter (not included).
- Country-specific AC adapters sold separately (PWR-SPLY-ELC).
- Input voltage: 5.5VDC ±5%
- E-1W: 703,871 hours
- Operating & Storage Temperature: -4 to 167˚F (-20 to 75˚C).
- Operating & Storage Relative Humidity: 0 to 90% non-condensing RH.
- CE, RoHS.
- Two years.
Data Sheet:
Users Manual:
NTI E-1W Installation and Operation Manual
NTI E-1W Quick Installation Guide
How To:
How to send SMS Alert Messages without using a USB modem and SIM Card
Reasons To Buy an NTI Product